UL has established certain requirements which pertain to the installation, use, and programming of this equipment. The local Authority
Having Jurisdiction (AHJ) and/or UL may have other requirements which apply to the installation of this system that are not detailed in
this manual. It is the responsibility of the installing dealer to check with the AHJ and/or UL before installing this system. The following
pages detail guidelines that must be followed in order to comply with the UL listings as stated above.
UL Notes In This Manual
Key “0” (Access) - The control has not been investigated to UL 294 Access Control System requirements.
Unsupervised Burglary Zones - UL does not permit the use of unsupervised zones.
UL Notes About Program Functions
Entrance Delay Time (1 and 2) - Maximum of 45 seconds.
AWAY Exit Delay Time - Maximum of 60 seconds.
Burglar Alarm Cutoff Time - Four minutes minimum for household BA/FA and 15 minutes for commercial burglar alarm and police station
connected burglar alarm system.
Fire Cutoff Time - No automatic cutoff permitted. Will be programmed to “0”, no cutoff.
Holdup Cutoff Time - maximum of four (4) minutes.
Communicator Enable - Local or police station connected burglar alarm installations: The communicator must be enabled.
Days Between Comm. Tests - Commercial installations: automatic test performed every 24 hours.
Time Between Dial Attempts - UL certified accounts: no more than 45 seconds between attempts.
Dial Type - Will not be programmed for foreign pulse.
Dial Attempts Before Shutdown - Five dial attempts minimum, ten dial attempts maximum.
Arming/Disarming Reports - This function will be enabled by programming report codes.
Low Battery Reporting - This function will be enabled by programming a report code for Grade A Local Burglar, Grade A Police Connected,
and Grade B and C Central Station Burglar installations.
Two Button/Double Press Arming - These functions will be disabled. Four digit passcodes will be used.
Enable Force Arming - This function will be disabled.
Enable Bypassing - This function will be disabled.
Burglar Alarm Output - Will be programmed to STEADY.
Fire Alarm Output - Will be programmed to TEMPORAL.
Burglar Loop Audible Lockout - This function will be disabled.
Enable Bell Test Upon Arming - This function will be enabled for Grade A Local Central Station Connected installations.
Enable Keypad Sounder for BA Zones - The system will have an audible alarm output upon alarm.
Auto-Arming - This function will be disabled.
Listen-In Modules must not be used.
Burglar zones will not be programmed as Verifying or Self-Verifying.
Output Type can NOT be programmed as Ground Start
UL Notes About Zone Planning
Burglar Loops - Will be defined as Alarm on Open/Alarm on Short.
Fire, Holdup, and Auxiliary Emergency Zones - Will not be defined as bypassable.
Special Functions/Alarms - Burglar zones will have an audible output.
Medical Emergency - At least one control station will be used as part of the system.
Zone will not be defined as Fast
UL Programming Requirements
5
Underwriters Laboratories (UL) Listing
This control is listed by Underwriters Laboratories (UL) as follows:
Application Listing
Household Burglary (Grade A) UL 1023
Household Fire UL 985
Central Station Burglary (Grade C) UL 1610/1635
Central Station Burglary (Grade B) UL 1610/1635
Home Health Care Signaling Equipment UL 1637
Local Burglary (Grade A) UL 609
Police Station Burglary Connection (Grade A) UL 365
WWW.DIYALARMFORUM.COM